Multi-brand supply, installation, commissioning and maintenance of industrial VFDs for the industry in Mexico. Regulations applied according to the requirements of the project.

Savings 20–50% kWh LV 220–690 V / MV up to 6.6 kV Regenerative AFE THD<3% National and international regulations Multi-brand: ABB · Siemens · Schneider

Law of affinity — why VFDs save so much

P ∝ n³When speed is reduced to 80%, power drops to 51%

A centrifugal pump controlled by variator consumes drastically less than with butterfly valve regulation, where the engine always rotates at nominal speed.

51%
consumption at 80% speed
34%
70% speed consumption
20%
consumption at 58% speed
20–50%
typical savings on pumps/ventilators
<2 years
usual return on investment
0.90+
Power factor with AFE
Supply Portfolio

Topologies of variable frequency drives that we supply and install

Selection depends on voltage level, power, EMC requirements, regenerative capacity and process communication protocol.

LV standard

VFD 2 levels — VSI (Voltage Source Inverter)

More widespread topology. Rect. diodes + DC bus + IGBT bridge. Range 0.37–2 500 kW, voltages 220–690 V AC. THDi without filter 35–45%; with 20–25% line reactor; with LCL filter <5%. Suitable for most pumps, fans, compressors and belts.

220–690VUp to 2 500 kWIGBTLine reactorOptional LCL filter
Medium Voltage

VFD 3 levels — NPC (Neutral Point Clamped)

For medium voltage motors 2.3–6.6 kV and powers from 315 kW to several MW. The multilevel design reduces dv/dt over the motor winding and improves the waveform (THDv <5% without extra filter). Requires input isolation transformer.

2.3–6.6 kV315 kW–several MWIGBT/IGCTTHDv <5%Xfmr input
Advanced settings

Multi-drive / Common DC Bus

Several inverters share a common DC bus powered by a centralized rectifier or shared AFE. The braking energy of one axle is reused on another motor axis. It is borderlined the number of rectifiers, improves overall THD and is optimal in machines with multiple coordinated axes (production lines, winders, looms).

Shared DC BusMultiple investorsInternal recoveryCoordinated axes
Power quality

Harmonic management according to IEC 61000-3-12 / IEEE 519

The THDi level determines whether a line reactor, passive LCL filter, or an active front-end is required. VMS Energy designs the solution according to the network capacity and the requirements of the applicable standard.

35–45%

Standard VFD without filter

Rect. 6-pulse diode without mitigation. Exceeds IEEE 519 limits (<5% in industrial PCC)

20–25%

With 3%Uk line reactor

Economic solution.Current current peaks and improves displacement power factor

<5%

With passive LCL filter

Complies with IEC 61000-3-12 and IEEE 519 in industrial environments. Recommended when THD affects other equipment

<3%

VFD with AFE (active rectif)

Best possible performance. Complies even on sensitive networks (hospitals, data centers, platforms)

Selection engineering

Key parameters for specifying a drive

A complete data sheet allows you to select the right family and size, avoiding oversize or premature failure due to thermal overload.

ParameterDetail / Typical rangesImpact on selection
Motor power (kW / HP)0.37 kW – several MWDetermines the product family and chassis size
Network voltage220 V / 380–480 V / 525–690 V / MV 2.3–6.6 kVDefine LV vs. MV; may require xfmr isolation
Load typeVariable torque (pumps/fans) vs. constant torque (compressors, belts, extruders)Variable torque allows derating; constant torque requires nominal gauge
Load Cycle Profile% permissible overload (110% / 150% for 60 s)Determine if the next size is required
Topology requiredVSI 2L, NPC 3L, AFE, Multi-DDefines THD level, regeneration and cost
Installation altitudeAMSL (m n.m.)Derating −1%/100 m over 1 000 m
Ambient temperatureMax. 40°C standard; derating −1.5%/°C over 40°CMay require larger chassis or additional forced ventilation
Communication protocolModbus RTU/TCP, Profibus DP, EtherNet/IP, PROFINET, DeviceNetDefines compatibility with existing PLC/SCADA
Degree of protectionIP20 (electrical room) / IP54–IP66 (field, ATEX zone)Impact on thermal dissipation and cabinet size
Site conditions

Derating by altitude and temperature

Mexico has altitudes that significantly impact the current capacity of a drive. Applying the correct factors from the design avoids overtemperature and premature breakdowns.

Derating by altitude

Above 1 000 m a.s.l., apply −1% of rated current for every additional 100 m.

Altitude (m a.s.l.)FactorReference city
0–1 0001.00 (no derating)Veracruz, Tampico
1 5000.95Guadalajara
2 2400.88Mexico City
2 5000.85Toluca
3 0000.80Puebla alta / mines
4 0000.70High altitude mines

Derating by temperature

Base 40°C. Above, apply −1.5% of rated current for each additional degree.

Ambient temperature (°C)FactorContext
≤ 401.00 (nominal)Electrical heated room
450.925Technical room without A/C
500.85Outdoor with direct sun
550.775Non-ventilated cabinet
600.70Hot process, oven

Apply both factors multiplicatively when altitude and temperature exceed their limits simultaneously.

Protection functions

Integrated Protections (ANSI Designation)

Modern drives incorporate electronic protections that complement or replace external protection relays, reducing costs and response times.

ANSI 49

Overtemperature (thermal)

I²t thermal model of the motor and NTC/PTC sensor in the IGBT. Trip with adjustable pre-alarm.

ANSI 51

Outflow overcurrent

Instantaneous and delayed electronic limitation to protect motor windings and IGBTs.

ANSI 46

Phase imbalance

Detects output current asymmetry greater than the configured threshold; protects against winding failure.

ANSI 27

Network underlay

Trip with hysteresis when Vred falls below the threshold. Automatic reset configurable after replacement.

ANSI 59

Overvoltage of DC network / bus

DC bus monitoring; Activates braking resistor or regenerative mode before overvoltage trip.

ANSI 48

Incomplete start / rotor lock

Detects blocked motor or excessive load during starting; maximum force ramp with time limit.

Industrial integration

Supported communication protocols

Integration with PLC, DCS and SCADA is critical for process automation. We select drives with the native protocol of the existing control system.

Modbus RTU/TCP

Universal RS-485 or Ethernet standard. Compatible with all PLCs on the market. Up to 247 RTU nodes.

Profibus DP

Siemens protocol with wide penetration in the process industry. Up to 12 Mbps, cycle det. <1ms.

PROFINET

Siemens Industrial Ethernet. Real time IRT (<1 ms), ideal for motion axes and CNC machines.

EtherNet/IP

Allen-Bradley/Rockwell protocol. TCP/IP + CIP. Compatible with FactoryTalk and Studio 5000.

DeviceNet

CAN network for compact Rockwell PLCs. Trunk/branch topology, up to 64 nodes.

BACnet/LON

For HVAC systems and building management. Integration with BMS and energy monitoring systems.

CANopen/DriveProfile

Motion applications and process machinery. Axis synchronization with DSP402 profile.

OPC-UA/IIoT

Direct connectivity to IIoT platforms (Azure IoT Hub, AWS IoT, MindSphere) for process analytics.

Multi-brand supply

Manufacturers we work with

We select the brand based on the process requirements, communication protocol, voltage level and project budget.

ABB

  • ACS180/ACS580
  • ACS880 (AFE)
  • ACS6000 (MV)
Low voltageMedium voltageRegenerative

SIEMENS

  • SINAMICS G120 / G130
  • SINAMICS S120 (servo)
  • SINAMICS GM150 (MV)
Low voltageMedium voltageServo

Schneider

  • Altivar ATV320
  • Altivar Process ATV630
  • Altivar 6000 (MV)
Low voltageMedium voltageProcess

Triol

  • AT24 (LV)
  • AT27 (MV Oil&Gas)
  • Sensorless vector control
Low voltageMedium voltageOil & Gas
Regulatory framework

Reference regulatory framework

The standards presented are of a information The rules applicable to each project — including national standards, requirements of the client or competent authority — are determined and agreed at the basic engineering stage in accordance with the specific requirements of the scope contracted.

IEC 61800-3

EMC for drives. Defines C1–C4 categories, conducted/radiated emissions limits and immunity requirements. Mandatory for CE Marking.

IEC 61800-5

Electrical and thermal safety. Insulation, protections, surface temperature and protective earth requirements.

IEC 61800-7

Communication profile. Generic interface for industrial networks (PROFIdrive, CiA402). Facilitates multi-brand integration with PLCs.

IEC 61000-3-12

Harmonics in MV/LV network >16 A. Establishes limits of THDi and individual harmonic currents at the point of common connection (PCC).

IEEE 519-2022

ANSI/IEEE harmonics standard. Reference in projects for North America. Sets THDv ≤5% and THDi according to short circuit ratio in the PCC.

UL 508C

Power Conversion Equipment. Required when the project follows NEC (NFPA 70) or the customer requires UL listing for equipment installed in the US or with NFPA code.

Frequently asked questions

Common doubts about frequency converters

How much energy savings does a frequency changer generate?
Thanks to the law of affinity (P ∝ n³), reducing the speed of a motor to 80% reduces consumption to 51%. For pumps and fans operating partially loaded, typical savings are 20 to 50% Regarding valve control or Munner. With a power price of 2.50–3.00 €2.50 – €30.00 €20.00 €50–500 kW engines, the return on investment is usually less than 2 years.
What rules govern the electromagnetic compatibility of VFDs?
IEC 61800-3 defines EMC requirements for variable speed drives. It sets categories C1–C4 according to the environment (residential vs. industrial) and the emission limits driven and radiated. For current harmonics, it applies IEC 61000-3-12 (equipment >16 A) e IEEE 519-2022 when the project follows NFPA/Aussi codes.
What is an AFE-type VFD and when should it be used?
A Active Front End (AFE) uses an active rectifier bridge (IGBT) instead of diodes, achieving THDi <3% It is suitable for applications with frequent braking (grills, elevators, presses) or where the quality of energy is critical. It has a cost 30–50% higher than a standard VFD, but it is amortized with the energy savings in braking and the elimination of dissipation resistances.
How does altitude affect the performance of a variator?
Above 1,000 m a.s.l., less dense air reduces the cooling of the drive. The standard rule is to apply a derating of −1% of the nominal current per 100 m additional. In Mexico City (2 240 m) the derating is ~12–15%. Some manufacturers offer special models up to 4,000 m without derating through reinforced ventilation design or overcalibrated cabinets. VMS Energy calculates the combined altitude + temperature factor for each project.
Does VMS Energy install variable frequency drives of any brand?
Yes. VMS Energy supplies and installs variable frequency drives Multi-brand (ABB ACS, Siemens SINAMICS, Schneider Altivar, Danfoss FC, Triol HV) depending on the process requirements, the required communication protocol and the system voltage level. We also carry out commissioning, PID parameter adjustment and training for the client's maintenance personnel.
VMShop

Triol AT24 variants available with direct quote

If your project requires a Triol variator, you can apply for a quote directly from VMShop — without bidding, with technical validation included and response within 24 hours.

Reference projects

Installed and commissioned variances

More than 60 variable frequency drives inspected, rehabilitated or commissioned on offshore platforms, food industry, mining, infrastructure and oil extraction.

KU-H, AYATSIL and MALOOB-D platforms — Pemex

Active Kumaza, Campeche

Commissioning of a 900 hp Robicon Perfect Harmony drive on 4 160 V; technical and visual inspection in the field of 900 and 800 HP Siemens drives; review, evaluation and correction of VDF-08-02; and inspection, component replacement and field testing of the VDF-10-01.

Baker Hughes

Campeche (offshore)

Service, supply, installation and commissioning of fourteen E-Cabinet frequency changers for intemperie.

AMOCA and MIZTON — Pemex

Tabasco

Service, supply, installation and commissioning of eight E-Cabinet frequency changers for intemperie in AMOCA and six in MIZTON.

SLB

Tabasco and the Caribbean

Engineering, supply, installation and commissioning of two Triol brand 1,000 HP medium voltage drives in a NEMA 4X cabinet, and a 75 HP self-supporting drive for oil extraction on land.

Pemex

Tabasco (Outward)

Performance evaluation service to six variable frequency drives in application of electro-centrifugal pumping on marine platform.

Cotemar

City of Carmen and Veracruz

Supply of six 50, 75 and 200 HP ABB frequency changers for marine platform; installation, interconnection and configuration of three others; and engineering, supply and commissioning of a 300 HP ranger for ground-based oil extraction.

Soft Drinks Bottling Company, Colima

Colima

Engineering, supply, installation and commissioning of a 200 HP Triol brand variable speed drive.

Tamazula Sugar Mill

Jalisco

Engineering, supply, installation and commissioning of a 300 HP regenerative drive from Schneider Electric; and technical training on ABB ACS880/ACQ580 drives and Rockwell RSLogix 5000/500 controllers.

Mining operation

Durango

Supply and commissioning of a Schneider Electric Altivar 980 700 HP variator to move a 900 m water column.

Infrastructure project

State of Mexico

Integration and commissioning of twelve NEMA 12 cabinets with Siemens drives and Profinet control via SCADA, for ventilation and extraction jetfans within a tunnel.

Reduce your power consumption with the correct variator!

Share with us the engine data, load profile and site altitude. Our engineers calculate derating, topology and ROI. We will contact you in less than 24 business hours; The study time depends on the scope.