What is a drop in voltage and how much is acceptable?
The Voltage drop is the difference between the voltage at the origin of the circuit and the one that reaches the load, due to the impedance of drivers and transformers. It is sustained: it lasts while the load is connected. NOM-001-SEDE-2012 recommends not to exceed 3 % in derived circuits or 5 % In the total of the feeder plus the derivative. Above that the engines lose torque (at 90% voltage, about 81 % of the torque), start with difficulty and heat.
What is a voltage gap (voltage sag) and how is it different from a voltage drop?
A Voltage gap (V.A.S. o V.U.S.) is a brief reduction in voltage, typically between 10% and 90% of the nominal value, lasting from half a cycle to one minute (IEEE 1159). The voltage drop is permanent while the load operates; the gap is an event. The gaps usually come from failures in the CFE network or from starts of large motors within the plant, and are only detected with an analyzer that records continuously.
Why do frequency changers shoot without apparent failure?
The most common cause is a Voltage gap: the drive's DC bus goes low, the equipment is protected by low voltage and stops, although the network recovers in milliseconds. Other causes are transients due to capacitor maneuvering and harmonics that heat up the rectifier. A diagnosis with a power quality analyzer makes it possible to link each trip with its event and decide if a power adjustment is sufficient. • The European Commission has been invited to take part in either an UPS, DVR or BESS is needed.
What is an energy quality analyzer and what does it record?
It is a measuring device that is installed on the panel, without interrupting operation, and continuously records voltage and current. The Class A analysers (IEC 61000-4-30) capture voltage dips and sags, interruptions, surges, transients, harmonics, flicker and power factor, with the exact time and waveform of each event. These records are the basis of the voltage quality diagnosis.
What is the best for voltage gaps: UPS, DVR or BESS?
It depends on the depth and duration of the holes and how much cargo needs to be protected. For PLC, control and instrumentation, a UPS. For a complete process line with split-second gaps, a DVR injects missing voltage without charging large batteries. If there are also interruptions from seconds to minutes or a economical case on demand, a BESS When the hole is caused by an internal start, a soft starter or variator removes it at the source.
What do they measure in an energy quality diagnosis?
We measure Voltage drop and interruptions, Voltage gaps (voltage sags or dips), THDi and THDv (current and voltage harmonic distortion), Power Factor real and displacement, Fender (Pst and Plt according to IEC 61000-4-15), voltage imbalance, transients and frequency variations. The measurement is carried out at the critical points of the system for a minimum of 7 continuous days with class A analyzers.
What standard does it apply to Aronics in Mexico?
The international reference standard most used in industrial projects in Mexico is IEEE 519-2022, which sets limits of THDi and THDv depending on the short circuit level at the point of common coupling (PCC). They also apply IEC 61000-3-2 E IEC 61000-3-12 according to the power of the generating equipment, and NMX-J-098-ANCE For solar parks connected to the CFE network, the Network Code of the National Parks is additionally applied.
How long does the measurement campaign last?
The minimum recommended measurement is 7 continuous days to capture load variations between shifts and working days vs. weekend. For plants with highly variable processes (safra, pharmaceutical batch, seasonal production campaigns) we recommend 14 or 28 days The measurement to make the profile representative of the worst operational case.
Are frequency variable frequency drives the only generators of the Aronics?
No. The main harmonic generators in an industrial plant are: frequency changers (VFDs) with 6 and 12 pulse rectifiers, Double conversion UPS, Battery charging rectifiers, Arch furnaces, switched power supplies in automation equipment, photovoltaic inverters and variable frequency welding machines. Identification of the dominant source is the basis for correctly sizing the solution.
Does the correction of the Aronics improve the power factor?
It depends on the solution. The Active filters (APF) correct Aronics and can compensate for reactive power simultaneously, improving both THDi and the total power factor (PF, not only cos passive filters specific amonics but do not compensate for fundamental reactive. Unfiltered capacitor banks can make the problem of the Aronics worse if they are not designed with the correct de-intonation.
Does diagnosis require stopping production?
No. The installation of the power quality analyzers is carried out on the conductors in operation using Hall effect current clamps without direct contact with energized conductors. The diagnosis does not interrupt the operation of the plant. Installation of the correction solution (filters, banks or APF) may require a short shutdown window for connection to the main board.
How long does it take to see results after installing the filters?
The results are immediate after commissioning. A active filter (APF) is compensated in microseconds; the THDi reduction is measurable in the first network cycle. The final validation is done with a second 7-day post-installation measurement campaign to confirm compliance with the IEEE 519 limits and the elimination of CFE penalties.