PV1-F photovoltaic cable for solar parks and industrial roofs
Solutions for solar parks and generation plants with focus on electrical safety and continuity of the project.
Solutions for solar parks and generation plants with focus on electrical safety and continuity of the project.
In a solar park the section is almost never decided by the ampacity: it is decided by the Voltage drop. Here both are checked with the factory data of the KEI PV1-F, and it is said which of the two rules in your section.
Flexible tinned copper DC solar cable, with halogen-free cross-linked polyolefin insulation and sheath. KEI factory catalog data.
2Pfg 1169/08.2007 and BS EN 50618. Class 5 conductor according to IEC 60228 / DIN VDE 0295. Certificate TÜV, VDE, ute and IM.
Nominal 0.6/1.0 kV, maximum 2,000 V DC. −40°C to +90°C environment; The conductor withstands 120 °C for 20,000 h.
Until 30 years UV resistance according to HD 605/A1 or DIN 53367, ozone according to EN 50396 8.1.3, and oils and alkalis according to EN 60811-2-1.
Minimum curvature radius 4 times the diameter and maximum shooting force of 50 N/mm2. Halogen-free: low smoke and low toxicity if there is fire.
From 2.5 to 16 mm² are the catalog ones; from 1.5 to 240 mm² are tabulated and manufactured under project request. That's where the DC trunks come in.
The standard PV1-F is not for direct buried installation. Underground sections require additional cover or protection piping.
Through VMShop you can request a cable quote directly — with or without an EPC project. If the supply is part of an EPC project that VMS engineers and builds, the cable is integrated into the MTO with milestone logistics and single responsibility. If you only need the material, we also support you with the same technical rigor.
If you only need uninstalled supplies, we can also support you — with the same technical and logistical rigors we apply to our EPC projects.
All measurements are reference for preliminary selection. Final choice depends on length of stretch, design current, installation method and project voltage drop limits.
Check base ampacity at 20 C and adjust by room temperature, grouping and watering.
Validate the percentage allowed in DC and AC per tranche, considering total length and caliber.
Coordinate fuses, sectioning and grounding according to topology and inverters.
In rooftop or open field installations, the actual cable temperature may exceed 60°C. Apply ampacity correction factors for actual ambient site temperature to avoid premature insulation degradation.
The PV1-F KEI cable complies with BS EN 50618, 2Pfg 1169/08.2007 and IEC 60228 Class 5. For projects with CFE (interconnection), verify that the park specification includes the standard required by the interconnection opinion.
Terms like Class 5, Ampacity, BS EN 50618 o LSZH? Consult them in the Cable technical glossary
Depends on the length of the string, the short circuit current of the module (Isc) and the voltage drop limits of the project. For standard strings: 4–6 mm². For long strings or high current: 10–16 mm². For DC trunks: 25–50 mm². VMS does the sizing if you share the electrical design.
The standard PV1-F is not designed for direct buried installation. For underground sections in a solar park, cable with additional sheath (double insulation or protective pipe) is required. VMS can specify the correct solution for each leg.
The PV1-F KEI cable has an estimated useful life of 30 years under standard operating conditions, with resistance to UV rays, ozone and thermal cycling. It is compatible with the typical useful life of an industrial solar park.
Yes. VMS Energy runs turnkey EPC projects. The supply of photovoltaic cable is part of the EPC range: we specify it, we try and install it. You don't need to coordinate with a separate provider.
Yes. In addition to the photovoltaic DC cable, we supply MV power cable for the interconnection of the inverter/lift transformer with the interconnection substation. All the cable infrastructure of the park can be managed with VMS.
CFE reviews the electrical design through the interconnection opinion (CENACE/CFE). Cables on the AC side must meet LAPEM specifications for interconnection voltage level. VMS accompanies the process from basic engineering to approval of the opinion.
Supply of FV cable with UV certification, intemperie resistance and IEC 62930 traceability.