Physical-Chemical Analysis
and DGA for Dielectric Oil
10 standardized parameters + dissolved gas diagnosis (DGA) by chromatography. We detect incipient failures before they become catastrophic failures. Compliant NMX-J-169-ANCE · IEC 60422 · IEEE C57.104.
10 parameters with standard and acceptance criteria
Each analysis includes comparison against IEC 60422 limit values, with RAG condition classification (green · yellow · red) by parameter and by equipment.
IEC 60156 ASTM D877/D1816
Dielectric strength (BDV)
Cup test with standardized electrode, 5–6 averaged measurements. Detects humidity and solid particles in suspension.
MV ≥ 30 kV/mm | HV ≥ 50 kV/mm
New oil: ≥ 60 kV/mm
< 20 kV/mm → emergency
IEC 60814 Karl Fischer
Moisture content (H₂O)
Karl Fischer coulometric titulation. Humidity reduces dielectric rigidity and accelerates the aging of insulating paper.
MV < 25 ppm | HV < 10 ppm
New oil < 5 ppm
> 35 ppm → immediate dehydration
ASTM D974 · IEC 62021-1
Acidity (neutralization index)
Measures organic acids produced by oil oxidation. Corrosive acids degrade paper and internal metals.
Normal < 0.15 mgKOH/g
Caution 0.15–0.30 | Action > 0.30
> 0.50 mgKOH/g → reemplazo
ASTM D971 · IEC 60422
Interfacial voltage
Measurement of voltage at the oil-water interface. It decreases with the presence of oxidation products and sludge.
Normal > 28 mN/m
Caution 22–28 | Action < 22 mN/m
< 18 mN/m → regeneration
IEC 60247 ASTM D924
Dielectric power factor (tan δ)
Measured at 90 °C. Indicates dielectric losses; rises with pollution, aging and presence of water.
Normal < 0.05% (90 °C)
Caution 0.05–0.20%
> 0.50% → corrective action
ASTM D1524
ASTM Color
Visual indicator of oil aging. Progressive darkening signals oxidation and sludge formation.
New oil ≤ 0.5
In service: ≤ 3.5 acceptable
> 5.0 → very degraded oil
ASTM D445
Cinematic viscosity
Measurement at 40 °C. It affects oil circulation and cooling efficiency. Rises by thermal polymerization.
Mineral oil class II: ≤ 11 mm²/s (40 °C)
Manufacturer reference as baseline value
ASTM D92 ASTM D93
Flash point
Minimum temperature at which the vapors are inflamed. A significant decrease suggests contamination with solvents or fuels.
New oil ≥ 135 °C
In service ≥ 125 °C
Descenso > 15 °C → investigar
ASTM D2668 · IEC 60666
Oxidation inhibitor (DBPC)
Concentration of 2,6-ditertbutylparacresol. Inhibited oils lose protection when DBPC is depleted and oxidation accelerates.
Inhibited oil: 0.20–0.35% m/m
< 0.08% → reponer inhibidor
IEC 60450 · ASTM D4243
Degree of paper polymerization (DP)
Insulating paper sampling. DP indicates residual useful life of solid insulation — irreversible once degraded.
New DP 1000–1200
DP < 400 → 50% vida consumida
DP < 200 → risk of rupture
DGA: Dissolved Gas Analysis by Chromatography
DGA is the most powerful predictive technique for oil transformers. Detects incipient failures months in advance by quantifying 7 key gases.
Duval Triangle
IEC 60599It uses the relative percentages of CH4, C2H4 and C2H2 to classify the type of failure: partial discharges (PD), overheating T1/T2/T3 and D1/D2 arcs. Graphically included in each report.
Rogers method
IEEE C57.104Gas ratios (CH₄/H₂, C₂H₄/C₂H₆, C₂H₂/C₂H₄) to classify failure by temperature and energy. It complements Duval's triangle in cases in border areas.
Trend Analysis
IEC 60422The gas generation rate (ppm/month) is as important as the absolute value. An increasing trend in acetylene or hydrogen, although below the threshold, may indicate active failure.
The 7 gases of DGA: origin and diagnostic meaning
| Gas | Formula | Main origin | Threshold IEEE C57.104 (Cond. 2) | Indicator |
|---|---|---|---|---|
| Hydrogen | H₂ | Partial discharges, slight overheating | 100ppm | DP/overheat |
| Methane | CH₄ | Oil overheating (< 300 °C) | 120ppm | Mild thermal |
| Ethane | C₂H₆ | Oil overheating (150–300 °C) | 65ppm | Moderate thermal |
| Ethylene | C₂H₄ | Severe overheating oil (> 300 °C) | 50ppm | Severe thermal |
| Acetylene | C₂H₂ | Electric arcs (> 700 °C) | 35ppm | Electric arc |
| Carbon monoxide | CO | Degradation of insulating paper (cellulose) | 350ppm | Gradient paper |
| Carbon dioxide | CO₂ | Normal/accelerated paper degradation | 2500ppm | Paper reference |
* TDCG (Total Dissolved Fuel Gas) = H₂ + CH₄ + C₂H₂ + C₂H₄ + C₂H₆ + CO. Condition 1: < 720 ppm (normal). Condition 2: 720–1920 ppm (caution). Condition 3: 1920–4630 ppm (action). Condition 4: > 4630 ppm (emergency). Source: IEEE C57.104.
From the sample to the action plan in 6 stages
A structured process that guarantees sample traceability, analytical rigour and actionable recommendations for the customer maintenance team.
Fleet survey
Transformer inventory, kVA, voltage level, oil type, previous analysis history and load conditions. Defines sampling priority.
Sampling according to IEC 60475
Sample under load (hot) with hermetic glass syringe. No bubbles, no air pollution. Documented chain of custody to the laboratory.
Laboratory analysis
GC-FID/TCD chromatograph for the 7 gases. Cup test IEC 60156 (BDV rigidity). Karl Fischer (humidity). Coulometry and spectrophotometry for the rest of the parameters.
Expert diagnosis
Duval + Rogers interpretation + historical trend analysis. RAG classification by parameter. Comparison with values from the previous campaign.
Technical report
PDF report by equipment with graphed Duval triangle, IEC 60422 comparative table, RAG condition and prioritized recommendations (immediate / 6 months / annual).
Monitoring program
Calendar of the next sampling campaign, individual threshold alerts by equipment and historical database in Excel for integration to the client's CMMS.
Analysis deliverables
Each diagnostic campaign generates a complete dossier that the maintenance team can integrate directly into its CMMS.
CF report by team
PDF with all parameters, measured values and IEC 60422 criteria
Duval Triangle
Graph with equipment coordinate and identified failure zone
DGA trends
Gas evolution graph (minimum 3 historical campaigns)
RAG classification
Traffic light by parameter and by equipment for maintenance prioritization
Prioritized recommendations
Immediate / 6 months / annual with technical justification and applicable standard
Rogers quotients
Calculation of CH₄/H₂, C₂H₄/C₂H₆ and C₂H₂/C₂H₄ ratios with interpretation
Sampling program
Calendar of next campaign by team according to RAG condition
Excel database
Historical evolution of all parameters for integration into CMMS
FQ analysis as part of your predictive strategy?
VMS Energy integrates diaelectric oil diagnosis with IR, Megger, VLF and vibration in a unified predictive maintenance program.
See predictive maintenance service →What maintenance teams ask us
How often should a transformer's oil be analyzed?
What does the presence of acetylene (C2H2) indicate in the DGA?
When is oil/regenerate replaced?
Can the oil sample be taken with the energized transformer?
What is the Duval Triangle and how is it interpreted?
What level of dielectric stiffness (BDV) is unacceptable to continue operating?
Do dry transformers (class F or H) require physical-chemical oil analysis?
Does VMS Energy also perform oil treatment or rehabilitation?
Maintenance of full substation?
We combine FQ/DGA analysis with electrical testing (TTR, Megger, VLF) in a larger maintenance EPC scope.
See substation service →New transformer diagnostic?
Baseline FQ/DGA analysis is part of the industrial transformer commissioning protocol run by VMS Energy.
See industrial transformers →Processors in oil
Oil change, rehabilitation, electrical tests and supply of transformers immersed in dielectric oil, on platforms in Campeche.
BALAM-TE Platform — Pemex
Campeche (offshore)
Change of oil in the TRD-56 and TRE-76 transformers, with wiring, electrical tests, installation of a new drive and repair of leaks in the existing radiators.
AKAL-C7 Platform — Pemex
Campeche (offshore)
Rehabilitation and repair of 2,240 kVA TX-4900A oil-type power and distribution transformer.
AKAL-B5 platform — Pemex
Campeche (offshore)
Rehabilitation and repair of the TX-4910A and TX-4910C power transformers, 2,000 kVA each.
LV-B platform
Campeche (offshore)
Major corrective maintenance and electrical testing of the TR-27 and TR-28 distribution transformers, 3,500 kVA and 34.5/4.16 kV, with supply and installation of four tubular bench-type radiators.
Pemex
Campeche
Supply of three-phase transformers with a DEEMSA power of 15 000 and 3 750 kVA, immersed in biodegradable dielectric oil liquid.
Maritime Services Campeche / Pemex
Campeche
Commissioning of a 1,500 kVA power transformer with insulation resistance (Megger), ohmic winding resistance, power factor and TTR transformation ratio.
When was the last oil analysis of your transformers?
If you do not have a history of DGA as a baseline, the first analysis is urgent — regardless of whether the equipment operates normally. Internal arc failures signal in DGA up to 12 months before manifesting as a malfunction.